1.HP BYPASS
2.HP BYPASS OPERATION
RAISING OF STEAM PARAMETER DURING TURBINE ROLLING
PARALLEL OPERATION WITH TURBINE ON LOAD REJECTION
PREVENTING SAFETY VALVES OPENING AT RAISED STEAM PRESSURES.
RAISING OF STEAM PARAMETER DURING TURBINE ROLLING
PARALLEL OPERATION WITH TURBINE ON LOAD REJECTION
PREVENTING SAFETY VALVES OPENING AT RAISED STEAM PRESSURES.
3.HPBP OPENING CRITERIA
HPBP DOWN STREAM TEMPERATURE < 380 Deg C
CRH DRAIN POT LEVEL NOT HIGH
CONDENSER VACUUM > -0.8 Ksc
HPBP DOWN STREAM TEMPERATURE < 380 Deg C
CRH DRAIN POT LEVEL NOT HIGH
CONDENSER VACUUM > -0.8 Ksc
4.FAST OPENING OF HP BYPASS
GENERATOR BREAKER OPENS
TURBINE LOAD SHEDDING RELAY OPERATED
PR. COTROLLER DEVIATION HIGH (>10%)
DEPRESSING OF “ FAST OPEN “ PUSH BUTTON FROM UCB
GENERATOR BREAKER OPENS
TURBINE LOAD SHEDDING RELAY OPERATED
PR. COTROLLER DEVIATION HIGH (>10%)
DEPRESSING OF “ FAST OPEN “ PUSH BUTTON FROM UCB
5.LP BYPASS
6.OPENING CRITERIA
Injection water Pr. > 25 Ksc
Exhaust steam Pr. < 19 Ksc
Condenser Wall Temp. < 90 DegC
Condenser Vacuum > -0.8 Ksc
Injection water Pr. > 25 Ksc
Exhaust steam Pr. < 19 Ksc
Condenser Wall Temp. < 90 DegC
Condenser Vacuum > -0.8 Ksc
7.AUTO SHUT-OFF OF LP BYPASS
CONDENSER VACUUM LOW ( BACK PR. > 220 mm of Hg.)
SPRAY WATER PR. LOW (<10 Ksc)
CONDENSER WALL TEMP. HIGH ( > 90*C )
LPBP DOWN STREAM PR. HIGH ( > 19 Ksc )
CONDENSER VACUUM LOW ( BACK PR. > 220 mm of Hg.)
SPRAY WATER PR. LOW (<10 Ksc)
CONDENSER WALL TEMP. HIGH ( > 90*C )
LPBP DOWN STREAM PR. HIGH ( > 19 Ksc )
8.HP-LP BYPASS CAPACITY
60% OF FULL
LOAD CAPACITY
60% OF FULL
LOAD CAPACITY
9.REHEAT PROTECTION
Turbine Trips & HP-LP bypass does not open. It will trip the Boiler after 5 Sec of turbine trip.
ARMING ------
200 T/Hr STEAM FLOW THROUGH
REHEATER
Turbine Trips & HP-LP bypass does not open. It will trip the Boiler after 5 Sec of turbine trip.
ARMING ------
200 T/Hr STEAM FLOW THROUGH
REHEATER